Residential /
Industrial
Surge
Protection
Systems

TES 240MSA
TES 240R  
TES 208SE
TES 277SE  
TES 240SE
TES 42SE
TES 46SE
 


Back to
:







 

Guidelines for electrical testing of TESCO Residential and Commercial Surge Protection Systems

 

Contents:

  • Varistor Voltage Measurement

  • Temporary Overvoltage

  • Surge/Multiple Surge Withstand

  • End of Life Failure Mode

  •  

    Varistor Voltage Measurement

    Procedure: Measurement of the nominal varistor voltage (the voltage across the metal oxide varistor with 1 mAdc through the device) identifies the voltage rating of the MOV used in each design. Changes in the voltage can indicate the degradation of a device after testing. This parameter is measured according to the IEEE definition of varistor voltage (ANSI/IEEE C62.33-1982).

    The sample must exhibit the characteristics of an MOV with a voltage rating of at least 150V, but no higher than 175V.

    Back to the top

     

    Temporary Overvoltage (TOV)

    Procedure: Because of neutral and/or connector problems, which cause voltage shifts on the residential 120V legs, the temporary overvoltage (TOV) characteristics of the device requires measuring. Voltage is applied individually to each leg, starting at 150Vac. The applied voltage is raised in 5Vac increments at 5 minutes Per step. For this test, a Tektronics model 5103N oscilloscope mainframe equipped with a 5A21N Vertical Amplifier and a P6021 AC Current Probe is used to measure/monitor the MOV current.

    The voltage step below which thermal runaway occurs is considered the TOV capability point, provided that the device demonstrates constant standby current and thermal stability for five minutes. A TOV capability of 185Vac or higher is required.

    Back to the top

     

    Surge/Multiple Surge Withstand

    Procedure: two types of surge withstand test are performed. The first consists of the application of one 8/20 usec. current surge with an amplitude of 40kA. Performing this test with 120Vac applied is currently under consideration. The surge arrester shall be able to withstand a single 8/20 usec. current surge of 40kA. After this surge, the varistor voltage may not change more than 10% from the initial value and the disconnecting device (i.e. fuse) shall not have operated. Any arcing, whether between two points in air or on a circuit board, is also considered a failure.

    The second test is a multiple surge withstand test, performed at a level of 800J per surge, with a modified cable fault locator or "thumper". Each arrester section is surged individually, with 120Vac applied continuously before, during and after the surge. The cable "thumper" is modified to provide a Combination Wave, 13KV-1.2/50 usec. open circuit and 5.5.kA - 8/20 usec. short circuit. A total of 100 surges at six-second interval are applied to the arrester.

    The surge arrester must survive without damage, show no signs of arching between components as mentioned before, not fault the ac line, have less than a 10% change in varistor voltage as measured in the paragraph on varistor voltage, and the disconnect device (i.e. fuse) must not have operated. Also, the discharge voltage across the device shall not exceed 2kV during the test.

    Back to the top

     

    End-of-Life Failure Mode

    Procedure: Similar to the fault withstand test in ANSI/IEEE C62.11, one MOV leg of the arrester is first put into thermal runaway using an overvoltage ac power source. Then, both legs are energized simultaneously, applying full available fault current to the device at full rated voltage (120/240Vac). Two levels of fault current re used in this test. Values of 3kA and 7kA are applied to independent samples. After the failure mode test, a 10kVdc withstand test is performed. Performing an impulse withstand test with ac bias in lieu of the dc withstand test is currently under consideration.

    The test circuit is fed by a 37.5kVA overhead distribution transformer with a 240/120V low side. This transformer then feeds a 600V, 600A class fused disconnect equipped with 600A slow blow, renewable fuses. Following the disconnect is a 600V, 2400A contactor which is used to initiate and determine the test. This contactor will remain closed for at least ten seconds, provided catastrophic failure of the sample does not occur. Following the contactor is a standard 200A service entrance meter enclosure. The device under test is hardwired to the meter-base. In order to energize all components in the device, meter-shorting bars are installed in the jaws.

    The internal fusing of the arrester must clear the fault without significant damage to the device, or meter enclosure, and without phase-to-phase or phase-to-neutral arcing.

     

    After the test, the damaged leg (side) of the sample must withstand the application of 10kVdc for 5 minutes, without removing any part(s) from the device or damaged fuse element. Also, the undamaged leg (side) of the sample must withstand the application of 10kVdc for 5 minutes, with its fuse element removed (any wires/leads/connectors to the fuse element must retain). Any arcing during the 10kVdc applications, whether between two points in air or on circuit board, is also considered failure.

    Back to the top

    Copyright © 1998 TESCO. All rights reserved.
    Revised: May 23 , 2000.